XLPE insulated power cable with rated voltage up to 35KV
- Courier
- In detail
- BrandHuadong cable
- Country of manufactureChina
- Type of power cable connectionStripped
- Conductor materialCopper/Aluminum
XLPE insulated power cable with rated voltage up to 35KV is the main product of Huadong cable Co.,Ltd.
Application
The XLPE insulated power cable is used in electric transmission and distribution system operating in vertical section, indoor, tunnels, mines. It was widely used in crowded public places such as high-rise building, largerise library, gymnasium, station, subway, underground shop, etc. The XLPE insulated power cablenot only has excellent electrical performance, environment resistant character & chemical-corrosion resisitant performance, simple structure, light weight, without restriction by laying fall, but it also has high temperature (90℃) for long time.
Standard
We produce these cables according to standard GB12706 and GB12666 (equivalent to IEC 60502 and IEC 60331), as well as BS, DIN and other internationl standards. In additional, we can also produce the Low-smoke free-halogen, Flame-retardant cables, or others according to customer request.
Voltage
0.6/1, 3.6/6, 6/6, 6/10, 8.7/10, 8.7/15, 12/20, 18/30, 21/35, 26/35KV
Installation
(a) The enviromental temperature for install cables is not lower than 0℃ degree, in case that the temperature is lower than 0 degree when cable is laid, it must be heated,
(b) Layout fall: the cable layout fall is not limited by level fall.
(c) The nonarmor XLPE power cable's bending radius should not be less than 15 times of cable O.D., the armor XLPE power cable's bending radius should not be less than 12 times of cable O.D..
Cable specification data
1.Cable rated voltage, core number, sectional area scope
No. Of core Sectional area(mm²) Rated vovoltageUO/U (kv) |
1st class | 0.6/1 | 1.8/3 | 3.6/6 | 6/10 | 8.7/15 | 12/20 | 18/30 | 21/35 |
2nd calss | 1/1 | 3/3 | 6/6 | 8.7/10 | 12/15 | 18/20 | —— | 26/35 | |
1 Core | 1.5~800 | 25~800 | 25~1200 | 25~1200 | 35~1200 | 50~1200 | 50~1200 | 50~1200 | |
2 Core | 1.5~185 | 25~185 | |||||||
3 Core | 1.5~400 | 25~400 | 25~400 | 25~400 | 35~400 | 50~400 | 50~400 | 50~400 | |
4 Core | 2.5~400 | 25~400 | |||||||
5 Core | 2.5~400 | 25~400 |
2.Conductor D.C resistance of finished cable at 20 degree per kilometer is not more than the following values
Nominal Section Area(mm²) | 1.5 | 2.5 | 4 | 6 | 10 | 16 | 25 | 35 | 50 | 70 | 95 | 120 | 150 | 185 | 240 | 300 | 400 | 500 | 630 | 800 |
Copper
core |
12.1 | 7.41 | 4.61 | 3.08 | 1.83 | 1.15 | 0.727 | 0.524 | 0.387 | 0.268 | 0.193 | 0.153 | 0.124 | 0.0991 | 0.0754 | 0.0601 | 0.047 | 0.0366 | 0.0283 | 0.0221 |
Aluminum core | 18.1 | 12.1 | 7.41 | 4.61 | 3.08 | 1.91 | 1.2 | 0.868 | 0.641 | 0.443 | 0.32 | 0.253 | 0.206 | 0.164 | 0.125 | 0.1 | 0.778 | 0.0605 | 0.0469 | 0.0367 |
3.Voltage test and partial discharge test
Item
Rated vltage Uo/U (KV) |
0.6/1 | 1.8/3 | 3.6/6 | 6/6 6/10 | 8.7/10 8.7/15 | 18/20 | 18/20 18/30 | 21/35 | 26/35 | |
Voltage Test | Test Voltage | 3.5 | 6.5 | 12.5 | 21 | 30.5 | 42 | 63 | 73.5 | 91 |
Test Time | 5 | |||||||||
Partial Discharge Voltage Test | Test Voltage | - | - | 6.2 | 10.4 | 15.1 | 20.8 | 31.1 | 36.3 | 45 |
Discharge Capacity | - | - | 10 | 10 | 10 | 10 | 10 | 10 | 10 |
Types of XLPE insulated power cable images and description
Solid-core or tightly-pressed sector (equal section)inner-steel-tape(orwire) -armoured XLPE cables
five core cable with tile type conductor
1.Outer sheath
2.Wrapping layer
3.tile type conductor
4.insulation for tile type conductor
5.insulation for protection conductor
6.conductor for protection
Sketch of Cable Cross Section Structure
Single core XLPE insulated PVC steath with non-armoured |
Three cores XLPE insulated PE steath with steel wire armoured |
Three cores XLPE insulated PVC steath with non-armoured |
3 1/2 cores XLPE insulated PE steath with steel wire armoured |
Three cores XLPE insulated PE steath with steel tape armoured |
Four cores XLPE insulated PE steath with steel wire armoured |
Three cores XLPE insulated PE steath with steel wire armoured |
1.Conductor
2.Conductor screen 3.XLPE Insulation 4.Insulation Screen 5.Metal Screen 6.Filler 7.Seperating Sheath (Inner Covering) 8.Armour 9.Over sheath |